Creating a modbus port driver

Before modbus port drivers can be created, it is necessary to first create at least one asyn TCP/IP or serial port driver to communicate with the hardware. The commands required depend on the communications link being used.

TCP/IP

For TCP/IP use the following standard asyn command:

drvAsynIPPortConfigure(portName, hostInfo, priority, noAutoConnect, noProcessEos)

Documentation on this command can be found in the asynDriver documentation.

The following example creates an asyn IP port driver called “Koyo1” on port 502 at IP address 164.54.160.158. The default priority is used and the noAutoConnect flag is set to 0 so that asynManager will do normal automatic connection management. Note that the noProcessEos flag is set to 0 so it is using the asynInterposeEos interface. The asynInterposeEos interface handles end-of-string (EOS) processing, which is not needed for Modbus TCP. However, it also handles issuing repeated read requests until the requested number of bytes has been received, which the low-level asyn IP port driver does not do. Normally Modbus TCP sends responses in a single packet, so this may not be needed, but using the asynInterpose interface does no harm. However, the asynInterposeEos interface is definitely needed when using drvAsynIPPortConfigure to talk to a terminal server that is communicating with the Modbus device over Modbus RTU or ASCII, because then the communication from the device may well be broken up into multiple packets.

drvAsynIPPortConfigure("Koyo1","164.54.160.158:502",0,0,0)

Serial RTU

For serial RTU use the following standard asyn commands This is recommended even when using actual:

drvAsynSerialPortConfigure(portName, ttyName, priority, noAutoConnect, noProcessEos)
asynSetOption(portName, addr, key, value)

Documentation on these commands can be found in the asynDriver documentation.

The following example creates an asyn local serial port driver called “Koyo1” on /dev/ttyS1. The default priority is used and the noAutoConnect flag is set to 0 so that asynManager will do normal automatic connection management. The noProcessEos flag is set to 0 because Modbus over serial requires end-of-string processing. The serial port parameters are configured to 38400 baud, no parity, 8 data bits, 1 stop bit.

drvAsynSerialPortConfigure("Koyo1", "/dev/ttyS1", 0, 0, 0)
asynSetOption("Koyo1",0,"baud","38400")
asynSetOption("Koyo1",0,"parity","none")
asynSetOption("Koyo1",0,"bits","8")
asynSetOption("Koyo1",0,"stop","1")

Serial ASCII

For serial ASCII use the same commands described above for serial RTU. After the asynSetOption commands use the following standard asyn commands:

asynOctetSetOutputEos(portName, addr, eos)
asynOctetSetInputEos(portName, addr, eos)

Documentation on these commands can be found in the asynDriver documentation.

The following example creates an asyn local serial port driver called “Koyo1” on /dev/ttyS1. The default priority is used and the noAutoConnect flag is set to 0 so that asynManager will do normal automatic connection management. The noProcessEos flag is set to 0 because Modbus over serial requires end-of-string processing. The serial port parameters are configured to 38400 baud, no parity, 8 data bits, 1 stop bit. The input and output end-of-string is set to CR/LF.

drvAsynSerialPortConfigure("Koyo1", "/dev/ttyS1", 0, 0, 0)
asynSetOption("Koyo1",0,"baud","38400")
asynSetOption("Koyo1",0,"parity","none")
asynSetOption("Koyo1",0,"bits","8")
asynSetOption("Koyo1",0,"stop","1")
asynOctetSetOutputEos("Koyo1",0,"\r\n")
asynOctetSetInputEos("Koyo1",0,"\r\n")

modbusInterposeConfig

After creating the asynIPPort or asynSerialPort driver, the next step is to add the asyn “interpose interface” driver. This driver takes the device-independent Modbus frames and adds or removes the communication-link specific information for the TCP, RTU, or ASCII link protocols. The interpose driver is created with the command:

modbusInterposeConfig(portName,
                      linkType,
                      timeoutMsec,
                      writeDelayMsec)
Parameter Data type Description
portName string Name of the asynIPPort or asynSerialPort previously created.
linkType int Modbus link layer type:, 0 = TCP/IP, 1 = RTU, 2 = ASCII
timeoutMsec int The timeout in milliseconds for write and read operations to the underlying asynOctet driver. This value is used in place of the timeout parameter specified in EPICS device support. If zero is specified then a default timeout of 2000 milliseconds is used.
writeDelayMsec int The delay in milliseconds before each write from EPICS to the device. This is typically only needed for Serial RTU devices. The Modicon Modbus Protocol Reference Guide says this must be at least 3.5 character times, e.g. about 3.5ms at 9600 baud, for Serial RTU. The default is 0.

For the serial ASCII example above, after the asynOctetSetInputEos command, the following command would be used. This uses a timeout of 1 second, and a write delay of 0 ms.

modbusInterposeConfig("Koyo1",2,1000,0)

drvModbusAsynConfigure

Once the asyn IP or serial port driver has been created, and the modbusInterpose driver has been configured, a modbus port driver is created with the following command:

drvModbusAsynConfigure(portName,
                       tcpPortName,
                       slaveAddress,
                       modbusFunction,
                       modbusStartAddress,
                       modbusLength,
                       dataType,
                       pollMsec,
                       plcType);
Parameter Data type Description
portName string Name of the modbus port to be created.
tcpPortName string Name of the asyn IP or serial port previously created.
slaveAddress int The address of the Modbus slave. This must match the configuration of the Modbus slave (PLC) for RTU and ASCII. For TCP the slave address is used for the “unit identifier”, the last field in the MBAP header. The “unit identifier” is ignored by most PLCs, but may be required by some.
modbusFunction int Modbus function code (1, 2, 3, 4, 5, 6, 15, 16, 123 (for 23 read-only), or 223 (for 23 write-only)).
modbusStartAddress int Start address for the Modbus data segment to be accessed. For relative addressing this must be in the range 0-65535 decimal, or 0-0177777 octal. For absolute addressing this must be set to -1.
modbusLength int The length of the Modbus data segment to be accessed. This is specified in bits for Modbus functions 1, 2, 5 and 15. It is specified in 16-bit words for Modbus functions 3, 4, 6, 16, or 23. Length limit is 2000 for functions 1 and 2, 1968 for functions 5 and 15, 125 for functions 3 and 4, and 123 for functions 6, 16, and 23. For absolute addressing this must be set to the size of required by the largest single Modbus operation that may be used. This would be 1 if all Modbus reads and writes are for 16-bit registers, but it would be 4 if 64-bit floats (4 16-bit registers) are being used, and 100 (for example) if an Int32 waveform record with NELM=100 is being read or written.
modbusDataType string This sets the default data type for this port. This is the data type used if the drvUser field of a record is empty, or if it is MODBUS_DATA. The supported Modbus data type strings are listed in the table below. This argument can either be one of the strings shown in the table below, and defined in drvModbusAsyn.h, or it can be the numeric modbusDataType_t enum also defined in drvModbusAsyn.h. The enum values are less convenient and understandable then the string equivalents. NOTE: the enum values changed between R3-0 and R3-1, which may require changes to startup scripts. INT16 and UINT16 were swapped and everything beyond INT32_LE is different.
pollMsec int Polling delay time in msec for the polling thread for read functions. For write functions, a non-zero value means that the Modbus data should, be read once when the port driver is first created.
plcType string Type of PLC (e.g. Koyo, Modicon, etc.). This parameter is currently used to print information in asynReport. It is also used to treat Wago devices specially if the plcType string contains the substring “Wago”. See the note below.

Modbus register data types

Modbus function codes 3, 4, 6, and 16 are used to access 16-bit registers. The Modbus specification does not define how the data in these registers is to be interpreted, for example as signed or unsigned numbers, binary coded decimal (BCD) values, etc. In fact many manufacturers combine multiple 16-bit registers to encode 32-bit integers, 32-bit or 64-bit floats, etc. The following table lists the data types supported by modbus. The default data type for the port is defined with the modbusDataType parameter described above. The data type for particular record can override the default by specifying a different data type with the drvUser field in the link. The driver uses this information to convert the number between EPICS device support and Modbus. Data is transferred to and from EPICS device support as epicsUInt32, epicsInt32, epicsInt64, and epicsFloat64 numbers. Note that the data type conversions described in this table only apply for records using the asynInt32, asynInt64, or asynFloat64 interfaces, they do not apply when using the asynUInt32Digital interface. The asynUInt32Digital interface always treats the registers as unsigned 16-bit integers.

drvUser field Description
INT16 16-bit signed (2’s complement) integers. This data type extends the sign bit when converting to epicsInt32.
INT16SM 16-bit binary integers, sign and magnitude format. In this format bit 15 is the sign bit, and bits 0-14 are the absolute value of the magnitude of the number. This is one of the formats used, for example, by Koyo PLCs for numbers such as ADC conversions.
BCD_UNSIGNED Binary coded decimal (BCD), unsigned. This data type is for a 16-bit number consisting of 4 4-bit nibbles, each of which encodes a decimal number from 0-9. A BCD number can thus store numbers from 0 to 9999. Many PLCs store some numbers in BCD format.
BCD_SIGNED 4-digit binary coded decimal (BCD), signed. This data type is for a 16-bit number consisting of 3 4-bit nibbles, and one 3-bit nibble. Bit 15 is a sign bit. Signed BCD numbers can hold values from -7999 to +7999. This is one of the formats used by Koyo PLCs for numbers such as ADC conversions.
UINT16 Unsigned 16-bit binary integers.
INT32_LE 32-bit integers, little endian (least significant word at Modbus address N, most significant word at Modbus address N+1).
INT32_LE_BS 32-bit integers, little endian (least significant word at Modbus address N, most significant word at Modbus address N+1). Bytes within each word are swapped.
INT32_BE 32-bit integers, big endian (most significant word at Modbus address N, least significant word at Modbus address N+1).
INT32_BE_BS 32-bit integers, big endian (most significant word at Modbus address N, least significant word at Modbus address N+1). Bytes within each word are swapped.
UINT32_LE Unsigned 32-bit integers, little endian (least significant word at Modbus address N, most significant word at Modbus address N+1).
UINT32_LE_BS Unsigned 32-bit integers, little endian (least significant word at Modbus address N, most significant word at Modbus address N+1). Bytes within each word are swapped.
UINT32_BE Unsigned 32-bit integers, big endian (most significant word at Modbus address N, least significant word at Modbus address N+1).
UINT32_BE_BS Unsigned 32-bit integers, big endian (most significant word at Modbus address N, least significant word at Modbus address N+1). Bytes within each word are swapped.
INT64_LE 64-bit integers, little endian (least significant word at Modbus address N, most significant word at Modbus address N+3).
INT64_LE_BS 64-bit integers, little endian (least significant word at Modbus address N, most significant word at Modbus address N+3). Bytes within each word are swapped.
INT64_BE 64-bit integers, big endian (most significant word at Modbus address N, least significant word at Modbus address N+3).
INT64_BE_BS 64-bit integers, big endian (most significant word at Modbus address N, least significant word at Modbus address N+3). Bytes within each word are swapped.
UINT64_LE Unsigned 64-bit integers, little endian (least significant word at Modbus address N, most significant word at Modbus address N+3).
UINT64_LE_BS Unsigned 64-bit integers, little endian (least significant word at Modbus address N, most significant word at Modbus address N+3). Bytes within each word are swapped.
UINT64_BE Unsigned 64-bit integers, big endian (most significant word at Modbus address N, least significant word at Modbus address N+3).
UINT64_BE_BS Unsigned 64-bit integers, big endian (most significant word at Modbus address N, least significant word at Modbus address N+3). Bytes within each word are swapped.
FLOAT32_LE 32-bit floating point, little endian (least significant word at Modbus address N, most significant word at Modbus address N+1).
FLOAT32_LE_BS 32-bit floating point, little endian (least significant word at Modbus address N, most significant word at Modbus address N+1). Bytes within each word are swapped.
FLOAT32_BE 32-bit floating point, big endian (most significant word at Modbus address N, least significant word at Modbus address N+1).
FLOAT32_BE_BS 32-bit floating point, big endian (most significant word at Modbus address N, least significant word at Modbus address N+1). Bytes within each word are swapped.
FLOAT64_LE 64-bit floating point, little endian (least significant word at Modbus address N, most significant word at Modbus address N+3).
FLOAT64_LE_BS 64-bit floating point, little endian (least significant word at Modbus address N, most significant word at Modbus address N+3). Bytes within each word are swapped.
FLOAT64_BE 64-bit floating point, big endian (most significant word at Modbus address N, least significant word at Modbus address N+3).
FLOAT64_BE_BS 64-bit floating point, big endian (most significant word at Modbus address N, least significant word at Modbus address N+3). Bytes within each word are swapped.
STRING_HIGH String data. One character is stored in the high byte of each register.
STRING_LOW String data. One character is stored in the low byte of each register.
STRING_HIGH_LOW String data. Two characters are stored in each register, the first in the high byte and the second in the low byte.
STRING_LOW_HIGH String data. Two characters are stored in each register, the first in the low byte and the second in the high byte.
ZSTRING_HIGH Zero terminated string data. One character is stored in the high byte of each register.
ZSTRING_LOW Zero terminated string data. One character is stored in the low byte of each register.
ZSTRING_HIGH_LOW Zero terminated string data. Two characters are stored in each register, the first in the high byte and the second in the low byte.
ZSTRING_LOW_HIGH Zero terminated string data. Two characters are stored in each register, the first in the low byte and the second in the high byte.

NOTE: if it is desired to transmit BCD numbers untranslated to EPICS over the asynInt32 interface, then data type 0 should be used, because no translation is done in this case.

NOTE: the ZSTRING_* types are meant for output records. For input records they are identical to their STRING_* counterparts.

NOTE: For big-endian formats the _BE format is order in which an IEEE value would be stored on a big-endian machine, and _BE_BS swaps the bytes in each 16-bit word relative to IEEE specification. However, for little-endian formats the _LE format is byte-swapped within each 16-bit word compared how the IEEE value would be be stored on a little-endian machine. The _LE_BS format is the order in which an IEEE value would be stored on a little-endian machine. This is done for backwards compatibility, because that is how _LE has always been stored in previous versions of this modbus module, before the byte-swapped formats were added.

The following is an example ai record using 32-bit floating point values:

# ai record template for register inputs
record(ai, "$(P)$(R)") {
    field(DTYP,"asynFloat64")
    field(INP,"@asyn($(PORT) $(OFFSET))FLOAT32_LE")
    field(HOPR,"$(HOPR)")
    field(LOPR,"$(LOPR)")
    field(PREC,"$(PREC)")
    field(SCAN,"$(SCAN)")
}

Note for Wago devices

This initial read operation is normally done at the same Modbus address as the write operations. However, Wago devices are different from other Modbus devices because the address to read back a register is not the same as the address to write the register. For Wago devices the address used to read back the initial value for a Modbus write function must be 0x200 greater than the address for the write function. This is handled by adding this 0x200 offset for the readback address if the plcType argument to drvModbusAsynConfigure contains the substring “Wago” (case sensitive). Note that this does not affect the address for Wago read functions. The user must specify the actual Modbus address for read functions.

Number of drvAsynIPPort drivers for TCP

Each drvAsynIPPort driver creates a separate TCP/IP socket connection to the PLC. It is possible to have all of the modbus port drivers share a single drvAsynIPPort driver. In this case all I/O to the PLC is done over a single socket in a “serial” fashion. A transaction for one modbus driver must complete before a transaction for another modbus driver can begin. It is also possible to create multiple drvAsynIPPort drivers (sockets) to a single PLC and, for example, use a different drvAsynIPPort for each modbus port. In this case I/O operations from multiple modbus drivers can proceed in parallel, rather than serially. This could improve performance at the expense of more CPU load on the IOC and PLC, and more network traffic.

It is important to note, however, that many PLCs will time out sockets after a few seconds of inactivity. This is not a problem with modbus drivers that use read function codes, because they are polling frequently. But modbus drivers that use write function codes may only do occasional I/O, and hence may time out if they are the only ones communicating through a drvAsynIPPort driver. Thus, it is usually necessary for modbus drivers with write function codes to use the same drvAsynIPPort driver (socket) as at least one modbus driver with a read function code to avoid timeouts.

The choice of how many drvAsynIPPort drivers to use per PLC will be based on empirical performance versus resource usage considerations. In general it is probably a good idea to start with one drvAsynIPPort server per PLC (e.g. shared by all modbus drivers for that PLC) and see if this results in satisfactory performance.

Number formats

It can be convenient to specify the modbusStartAddress and modbusLength in octal, rather than decimal, because this is the convention on most PLCs. In the iocsh and vxWorks shells this is done by using a leading 0 on the number, i.e. 040400 is an octal number.